Legionella Control: Preventing Pneumonia in Plumbing
Legionella bacteria lurk in stagnant water and warm pipes. Learn how to manage plumbing systems, cooling towers, and hotels to prevent deadly outbreaks of Legionnaires' disease.
Legionella pneumophila is a bacterium that loves warm water (20°C - 50°C). When we inhale tiny water droplets (aerosols) containing this bug, it causes a potentially fatal pneumonia.
Common Sources: Cooling towers, hot tubs, showerheads, decorative fountains.
prevention Strategies
1. Temperature Control (The Golden Rule)
- Keep Hot Water HOT: > 60°C (Bacteria die).
- Keep Cold Water COLD: < 20°C (Bacteria sleep).
- The Danger Zone: 25°C - 45°C is the prime breeding ground.
- The Protocol: Store hot water at 60°C+. Deliver it to taps at 50°C (install thermostatic mixing valves (TMVs) right at the tap to prevent scalding if needed, but keep the loop hot).
2. The Enemy: Biofilm
Legionella doesn't just float in water; it hides inside Biofilm—a slimy layer of bacteria and organic gunk that coats the inside of old pipes.
- Why it matters: Chlorine often can't penetrate thick biofilm. The bacteria hide inside, safe from chemicals, and release into the water randomly.
- Solution: You need strong oxidizers (like Chlorine Dioxide) or physical cleaning to strip biofilm.
3. Avoid Stagnation ("Dead Legs")
A "Dead Leg" is a pipe that leads to nowhere (capped off during renovation) or a tap that is rarely opened (like a guest bathroom in a hotel that is empty for weeks).
- The Risk: Water sits still, loses its chlorine, warms up to room temperature, and becomes a petri dish.
- Action:
- Identify and remove all capped pipes.
- Implement a Flushing Log: Turn on every unused tap/shower for 5 minutes once a week.
4. Chemical Disinfection Options
For high-risk buildings (Hospitals, Hotels, Nursing Homes):
| Method | Effectiveness | Pros | Cons |
|---|---|---|---|
| Chlorine | Moderate | Cheap, widely available | Evaporates in hot water; weak against biofilm. |
| Chlorine Dioxide (ClO2) | Excellent | Penetrates biofilm; stable in hot water | Requires on-site generator; expert handling needed. |
| Copper-Silver Ionization | Good | Long-lasting residual; kills bugs directly | Can cause green staining; difficult to control levels. |
5. Cooling Tower Maintenance (The Aerosol Factory)
Cooling towers are the #1 source of major outbreaks because they spray warm water mist into the air.
- Biocide Dosing: Must alternate between two types of biocides (to prevent resistance).
- Drift Eliminators: Install high-efficiency baffles to trap water droplets before they leave the tower.
- Deep Clean: Drain and scrub the tower basin twice a year.
Facility Maintenance Checklist
If you manage a building, follow the ASHRAE 188 Standard:
- Daily: Check calorifier (water heater) temperature is > 60°C.
- Weekly: Flush all low-use outlets (showers/taps) for 3 minutes.
- Monthly: Measure temperature at the "Sentinel Points" (nearest and furthest taps from the heater).
- Quarterly: Descale showerheads and aerators (scale hides bacteria).
- Yearly: Inspect cold water tanks for sediment/sludge.